Model Description
S13 performance parameters
|
Rated |
Rated voltage(kV) |
coupling |
No load |
loss(W) |
impedance |
Reference dimensions(mm) |
reference weight(kg) |
gauge |
||||||
|
high pressure |
Low pressure |
No load |
load |
length |
width |
height |
Body |
Oil weight |
Gross weight |
|||||
|
50 |
6 10
10.5 或 ±5%
|
0.4 |
Yyn0 |
0.5 |
100 |
910/870 |
4.0 |
760 |
710 |
960 |
180 |
95 |
350 |
400×400 |
|
80 |
0.5 |
130 |
1310/1250 |
840 |
810 |
1030 |
230 |
105 |
440 |
400×450 |
||||
|
100 |
0.45 |
150 |
1580/1500 |
890 |
830 |
1050 |
295 |
120 |
520 |
400×450 |
||||
|
125 |
0.45 |
170 |
1890/1800 |
960 |
880 |
1100 |
370 |
150 |
630 |
400×450 |
||||
|
160 |
0.45 |
200 |
2310/2200 |
1045 |
920 |
1130 |
420 |
170 |
720 |
550×550 |
||||
|
200 |
0.4 |
240 |
2730/2600 |
1085 |
950 |
1170 |
485 |
190 |
850 |
550×550 |
||||
|
250 |
0.4 |
290 |
3200/3050 |
1200 |
800 |
1200 |
550 |
200 |
910 |
550×550 |
||||
|
315 |
0.4 |
340 |
3830/3650 |
1250 |
850 |
1200 |
600 |
210 |
1000 |
660×750 |
||||
|
400 |
0.35 |
410 |
4520/4300 |
1340 |
1130 |
1300 |
850 |
255 |
1350 |
660×750 |
||||
|
500 |
0.35 |
480 |
5410/5150 |
1370 |
1160 |
1350 |
1015 |
290 |
1590 |
660×750 |
||||
|
630 |
0.3 |
570 |
6200 |
4.5 |
1480 |
1300 |
1380 |
1180 |
360 |
1880 |
660×750 |
|||
|
Note: For three-phase transformers with a rated capacity of 500kVA and below, the load loss value above the diagonal line in the table applies to the Dyn11 connection group, and the load loss value below the diagonal line applies to the YynO connection group load loss value. |
||||||||||||||